X20IF041-1 CANopen master


          

Product Description:


MATERIAL NUMBER:
X20IF1041-1
DESCRIPTION:


  • CANopen master
  • Integrated terminating resistor

The interface module is equipped with a CANopen interface. This allows third-party components to be integrated in the B&R system and makes it possible to quickly and easily transfer data in both directions.

The interface module can be operated in X20 CPUs or in the expandable POWERLINK bus controller X20BC1083.



Short description
Communication module CANopen master
General information
B&R ID code 0xA709
Status indicators Module status, network status, data transfer, terminating resistor
Diagnostics
Module status Yes, using LED status indicator and software
Network status Yes, using LED status indicator and software
Data transfer Yes, using LED status indicator
Terminating resistor Yes, using LED status indicator
Power consumption 1.1 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B(0 - 55°C)
Humidity: B(up to 100%)
Vibration: B(4 g)
EMC: B(bridge and open deck)
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: bridge and open deck
EAC Yes
KC Yes
Interfaces
Interface IF1
Fieldbus CANopen master
Variant 5-pin male multipoint connector
Max. distance 1000 m
Transfer rate Max. 1 Mbit/s
Terminating resistor Integrated in module
Controller netX100
Memory 8 MB SDRAM
Electrical properties
Electrical isolation PLC isolated from CANopen (IF1)
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block TB2105 separately.
Slot In the X20 PLC and expandable bus controller X20BC1083




Inquiry:

CATEGORIES

CONTACT US

Wisdom Technology Automation LTD

Phone: +86 183 9631 9060

Tel: +86 400 8388 879

Email: info@wisdauto.com

Add: Unit 811, Beverley Commercial Centre,87-105 Chatham Rd South Tsi Sha Tsui

Leave a message

Facebook

Twitter

LinkedIn

+86 400 8388 879

+86 18396319060

whatsapp

info@wisdauto.com